Polling Alarms, Events, and History to the Central Ignition Gateway

Overview​

The EFM ABB Totalflow module can poll alarm, event, and history data from an ABB Totalflow device at a specified polling rate.

MQTT Transmission can publish this data as Sparkplug RECORD messages to an MQTT server. MQTT Engine receives the records on the central Ignition Gateway, and MQTT Recorder stores them in a configured database.

This tutorial describes how to configure the EFM ABB Totalflow and MQTT modules to collect and publish alarm, event, and history records from a remote/edge Ignition Gateway to a central Ignition Gateway.


Central Gateway Setup​

The central Ignition Gateway receives ABB Totalflow records through MQTT Engine and stores them in a database using MQTT Recorder.

Configure MQTT Distributor​

MQTT Distributor can remain at its default configuration. For production deployments, configure TLS if MQTT connections traverse an untrusted network.

Configure MQTT Engine​

MQTT Engine can remain at its default configuration.

Configure a Database​

Create an Ignition database connection for MQTT Recorder to use. For instructions, see Connect to a Database.

Configure MQTT Recorder​

  1. In the Ignition Gateway interface, navigate to the Config tab on the left hand side.
  2. Select MQTT Recorder > Settings.
  3. Select the database connection from the Datasource dropdown.
  4. Optionally, configure a Partition Period to separate recorded data into tables by time period.

The Central Ignition Gateway is now configured to receive MQTT Sparkplug messages from the Remote/Edge Gateway. By default, MQTT Distributor listens for MQTT connections on TCP port 1883. Ensure the operating system firewall and security software allow inbound connections on this port.


Edge Gateway Setup​

The remote/edge Ignition Gateway collects data from the ABB Totalflow device and publishes it to the MQTT server. With the Central Ignition Gateway ready to receive MQTT/Sparkplug RECORD messages, configure MQTT Transmission on the remote/edge Ignition Gateway.

Configure the MQTT Transmission Tag Structure​

If using the Default Transmitter in MQTT Transmission, create a tag structure with the following hierarchy:

[Tag Provider]/Edge Nodes/[Group ID]/[Edge Node ID]/[Device ID]/...

For example:

  • Group ID: G1
  • Edge Node ID: E1
  • Device ID: Totalflow G4 Sim

The Group ID, Edge Node ID, and Device ID must match the corresponding Sparkplug settings in the EFM ABB Totalflow device configuration. These values associate the Totalflow device with the appropriate MQTT Transmission transmitter and MQTT connection.

Configure the MQTT Transmission Server​

Configure MQTT Transmission to connect to the Central Ignition Gateway:

  1. In the Ignition Gateway, select Configure.
  2. Select MQTT Transmission > Settings.
  3. Select the Servers tab.
  4. Edit the MQTT server configuration.
  5. Set the server URL to the Central Ignition Gateway's address.
  6. Verify that the server shows 1 of 1 in the Connected column.

Configure the EFM ABB Totalflow Module​

Complete the following steps:

  1. Define the global Array-Register definitions for the ABB Totalflow devices on the Ignition Gateway.
    • Skip this step if you are not configuring the driver to poll AAR data.
  2. Upload the Periodic Mapping files for the ABB Totalflow devices.
    • This step can be skipped if the default mappings provided by the driver meet your requirements.
  3. Create a device connection to the ABB Totalflow device.
  4. Select the subset of global Array-Register definitions used by the device.
    • Skip this step if you are not configuring the driver to poll AAR data.
  5. Configure the device's scan rates for the record types you want to collect.

Alarms​

Alarm data can be collected from either:

  • Periodic History Records (Array 250)
  • Alarm Log Records (Array 245)

The available alarm source is determined by the Alarm Source setting in the device configuration.

Poll Alarms from Periodic History Records​

Set Alarm Source to PERIODIC_HISTORY_RECORDS.

To poll alarms directly:

SettingValue
Alarm Scan Rate0
Event Scan Rate-1
Periodic History Scan RatePositive value
Daily History Scan Rate-1
Record Info Scan Rate-1

To poll alarms when the Record Info poller detects new data:

SettingValue
Alarm Scan Rate0
Event Scan Rate-1
Periodic History Scan Rate0
Daily History Scan Rate-1
Record Info Scan RatePositive value

Poll Alarms from Alarm Log Records​

Set Alarm Source to ALARM_LOG_RECORDS.

To poll alarms directly:

SettingValue
Alarm Scan RatePositive value
Event Scan Rate-1
Periodic History Scan Rate-1
Daily History Scan Rate-1
Record Info Scan Rate-1

To poll alarms when the Record Info poller detects new data:

SettingValue
Alarm Scan Rate0
Event Scan Rate-1
Periodic History Scan Rate-1
Daily History Scan Rate-1
Record Info Scan RatePositive value

Events​

To poll Event records directly, set Event Scan Rate to a positive value and disable the other record pollers:

SettingValue
Alarm Scan Rate-1
Event Scan RatePositive value
Periodic History Scan Rate-1
Daily History Scan Rate-1
Record Info Scan Rate-1

To poll Events when the Record Info poller detects new data, set Event Scan Rate to 0 and Record Info Scan Rate to a positive value.

SettingValue
Alarm Scan Rate-1
Event Scan Rate0
Periodic History Scan Rate-1
Daily History Scan Rate-1
Record Info Scan RatePositive value

History​

To poll Periodic and Daily History records directly, set their scan rates to positive values:

SettingValue
Alarm Scan Rate-1
Event Scan Rate-1
Periodic History Scan RatePositive value
Daily History Scan RatePositive value
Record Info Scan Rate-1

To poll History records when the Record Info poller detects new data, set the Periodic and Daily History scan rates to 0 and Record Info Scan Rate to a positive value:

SettingValue
Alarm Scan Rate-1
Event Scan Rate-1
Periodic History Scan Rate0
Daily History Scan Rate0
Record Info Scan RatePositive value

Verify Records​

Once the EFM ABB Totalflow device is configured and MQTT Transmission is connected to the MQTT server, the configured record data is published as Sparkplug RECORD messages.

When new records are collected:

  1. The EFM ABB Totalflow module polls the device for new data.
  2. MQTT Transmission publishes the records to the MQTT server.
  3. MQTT Engine receives the records on the Central Ignition Gateway.
  4. MQTT Recorder stores the records in the configured database.

Verify that the expected records are appearing in the MQTT Recorder database.