Browse Tags
After the device status changes to Connected, the Opto 22 groovEPIC and SNAP PAC Driver automatically discovers all variables and I/O points configured as Public in PAC Control.
You can browse these tags from either the Ignition Gateway or Ignition Designer.
Browse Tags in the Ignition Gateway
- In the Ignition Gateway, navigate to OPC Client > OPC Quick Client.
- Expand Ignition OPC UA Server.
- Expand your configured Opto 22 device to browse the available tags.



Browse Tags in Ignition Designer
- Open Ignition Designer.
- Select View > Panels > OPC Browser.
- Expand Ignition OPC UA Server.
- Expand your configured Opto 22 device to browse the available tags.

Troubleshooting
If expected tags do not appear:
- Verify the device status is Connected.
- Confirm the PAC Control strategy is running on the controller.
- Ensure the variables or I/O points are configured as Public in PAC Control.
- Check that the controller is reachable on the network.
- Review the Ignition Gateway logs (Status > Diagnostics > Logs) for communication or driver errors.